Home / Resources / Fire Safety Records

What a Compliant Fire Safety Maintenance Record Has to Contain

A service report and a compliant record are not automatically the same thing. Section 55 of the Building Fire Safety Regulation 2008 (Qld) sets out exactly what has to be in the record for each prescribed fire safety installation. Work can be done perfectly and still leave you with paperwork that does not meet the regulation.

Building Fire Safety Regulation 2008 Section 55 Record Contents Two Year Retention Audit-Ready Reporting
The Short Answer

What Must a Fire Safety Record Contain?

Under section 55 of the Building Fire Safety Regulation 2008 (Qld), the record for each prescribed fire safety installation must contain a defined set of items. If any of them are missing, the record is incomplete regardless of how well the work was done.

Required itemWhat it means in practice
Description of the installationWhich system the record relates to, identified clearly enough that it can be matched to the asset. Not simply "fire equipment".
Name and licence number of the person who did the workThe individual who carried out the maintenance, and their licence number. This is the item most often missing from generic service dockets.
The dateWhen the work was carried out, which is what establishes whether the routine fell inside its required interval.
What was doneThe actual maintenance performed, not a generic line item. This is what a later technician compares against.
Whether it is in proper working orderThe worker's assessment of whether the installation was left in proper working order.
Repairs and corrective actionDetails of any repairs or corrective action arising from the visit, including what remains open.
Signed certificationSigned by the person who carried out the maintenance, certifying the record is correct.
Records are kept with the occupier statement for two years and produced when asked. The record set and the statement are designed to be read together, which is why keeping them in two disconnected places causes problems at exactly the wrong moment.
Why It Matters

Why the Licence Number Matters More Than People Expect

The requirement to record the name and licence number of the person who did the work is not administrative box-ticking. It is the point where the record proves the work was done by somebody legally entitled to do it.

Fire protection work in Queensland is occupational licensed work through the QBCC. The licence classes are specific, and being licensed for one type of fire protection work does not make somebody licensed for another. A record that names an individual and their licence number can be checked. A record that names only a company cannot.

If you are reviewing a contractor's reporting and the licence numbers are absent, that is worth raising before you need the records rather than after. We cover the licensing question in detail in our guide to who can legally service fire systems in Queensland.

Baseline Data

What Every AS 1851 Test Is Actually Measured Against

AS 1851-2012 is built on comparison. A test result on its own means very little. What gives it meaning is the baseline data recorded when the system was commissioned.

A fire pumpset that produces a given pressure and flow today is only performing correctly if that matches what it produced when it was commissioned and proven. A sprinkler system's alarm valve, a hydrant's flow at the most disadvantaged outlet, a detection panel's battery capacity: in each case the standard is asking whether the system still does what it was designed and proven to do.

This is why baseline data is worth protecting. Buildings that have lost their commissioning records have lost the reference point that makes their ongoing testing meaningful, and re-establishing it is a real piece of work. If you hold that documentation, it belongs with the maintenance records, not in a drawer in a site office.

A practical consequence. When we take over a building, one of the first things we look for is baseline and commissioning data. Where it does not exist, we say so rather than quietly testing against nothing and reporting a pass.
Defect Classification

Critical and Non-Critical Defects

AS 1851-2012 does not treat every fault the same way, and neither should a report.

Critical defects

A critical defect stops the system doing its job in a fire. An isolated detection zone, a pump that will not start, a blocked or closed water supply valve. These must be actioned immediately. Carrying a critical defect forward to the next routine is not an option the standard offers.

Non-critical defects

A non-critical defect still has to be rectified, but it does not prevent the system operating. Damaged signage, a corroded bracket, a missing cabinet key. These are tracked and closed out on a reasonable timeframe rather than same-day.

The reason the distinction belongs in your records is accountability. A report that lists twenty items without classifying them leaves the building owner to guess which one is the emergency. A report that classifies them tells you what to do this afternoon and what can go in next month's budget.

How We Report

How Safe QLD Reports

Questions We Get Asked

Frequently Asked Questions

How long do fire safety maintenance records have to be kept in Queensland?
Records are kept with the occupier statement for two years and produced when they are asked for. In practice we recommend keeping them longer where you can, because commissioning and baseline data becomes more valuable over time, not less, and because a two year window can fall awkwardly across a change of building manager or a sale.
Is a service docket the same as a compliant maintenance record?
Not necessarily. Section 55 of the Building Fire Safety Regulation 2008 (Qld) requires specific content, including a description of the installation, the name and licence number of the person who did the work, the date, what was done, whether the installation was left in proper working order, details of repairs or corrective action, and a signed certification that the record is correct. Plenty of generic dockets are missing at least one of those.
What is baseline data and why does AS 1851 keep referring to it?
Baseline data is the performance the system demonstrated when it was commissioned and proven. AS 1851-2012 routines are largely comparisons: the question is not simply whether a pump runs, but whether it still delivers the flow and pressure it delivered at commissioning. Without baseline data you can record a result but you cannot say whether it represents degradation, which is most of the value the standard is trying to deliver.
What is the difference between a critical and a non-critical defect?
A critical defect prevents the installation performing its function in a fire and must be actioned immediately. A non-critical defect must still be rectified but does not stop the system working. Classifying them is what turns a list of faults into something a building owner can actually prioritise and budget.
Do I need records for systems that are not covered by AS 1851?
Yes, where they are prescribed fire safety installations. A good example is emergency and exit lighting, which is not an AS 1851 system. Its inspection and maintenance sits under AS/NZS 2293.2, with design and installation under AS/NZS 2293.1, and the six-monthly discharge test runs fittings for their full rated duration with every fitting individually recorded. It still needs proper records.