An occupier statement is not just a form you sign and file. Under section 55A of the Building Fire Safety Regulation 2008 (Qld) it has to be prepared to a set standard, kept with your maintenance records for two years, and lodged with the Queensland Fire Department. Missing the lodgement is the single most common fire compliance failure we find on buildings that otherwise look well maintained.
An occupier statement is a signed declaration by the occupier of a building that the prescribed fire safety installations in that building have been inspected, tested and maintained as required, and that the records to prove it exist.
It is the document that converts a year of maintenance visits into a legal position. The maintenance itself is done under AS 1851-2012. The statement is the occupier standing behind that maintenance in writing, to the standard set by Queensland Development Code MP 6.1.
The word that matters is occupier. The obligation does not sit with your fire contractor, your building manager or your body corporate committee by default. It sits with the occupier of the building, which is why it is worth knowing exactly what the regulation asks for rather than assuming somebody else has it covered.
Section 55A of the Building Fire Safety Regulation 2008 (Qld) creates three separate obligations. They are separate, and each one carries a penalty if it is missed.
The occupier must prepare an occupier statement that complies with Queensland Development Code MP 6.1, at the required intervals. It has to reflect what was actually inspected, tested and maintained, which means the underlying AS 1851 routines need to have been done and recorded first.
A copy must be kept with the maintenance records for the building for two years, and produced when it is asked for. In practice this means the statement and the records that support it need to live together, not in two different systems.
The occupier must give the commissioner of the Queensland Fire Department a copy of the statement within 10 business days of preparing it. This is the obligation buildings miss. Preparing and filing the statement satisfies two of the three requirements and still leaves you non-compliant.
Queensland Development Code MP 6.1 is the maintenance standard behind the statement, and it applies to Class 1b buildings and Class 2 to Class 9 buildings under the National Construction Code.
In everyday terms that captures the great majority of buildings that are not a standalone house: apartment and unit blocks, offices, shops and shopping centres, warehouses and factories, hotels and short stay accommodation, hospitals and aged care, schools and childcare, and public assembly buildings.
What it does not do is set one identical schedule for all of them. The prescribed fire safety installations in a small strata block and in a cold storage warehouse are completely different, so the maintenance that sits underneath the statement is different too. That is why the honest first step is always a survey of what is actually installed, not a quote against an assumed asset list.
A statement is only as good as the maintenance behind it. Before an occupier signs, these things need to be genuinely true, not assumed.
Systems get added during fitouts and forgotten. A stairwell pressurisation fan, a second booster, an aspirating detector added for a cold room. If it is a prescribed fire safety installation and it is not on the maintenance schedule, it is not being maintained and the statement is overstating your position.
AS 1851-2012 sets monthly, six-monthly, yearly and five-yearly routines depending on the system. Frequencies have defined tolerances. A routine done far outside its window is not simply late, it can break the continuity the records are supposed to demonstrate.
AS 1851 separates critical defects, which stop a system doing its job in a fire, from non-critical defects. A critical defect that is still open is not a paperwork problem, it is a system that will not perform. It needs to be rectified, not noted.
Each record has to contain specific things, including the licence number of the person who did the work. A report that does not carry them is not a compliant record even if the work was done properly. We cover this in detail in our guide to fire safety maintenance records.
If a QBCC licensed fire protection technician finds that an installation does not conform to the required standard, there is a formal path, and it does not stop at a note in the report.
QBCC Form 71 is the notice the licensee gives the owner advising that a fire protection installation is non-conforming. QBCC Form 72 is the escalation to the QBCC where the non-conformance has not been rectified. Both are non-conformance instruments. They are not aspect certificates, and they are not interchangeable with the Form 12 and Form 15 used to certify building work.
For an occupier this matters because a Form 71 sitting unactioned is a documented, dated record that you were told about a problem. It is the opposite of the position you want to be in when you sign a statement.
We build the statement obligation into the maintenance program rather than treating it as an afterthought at the end of the year.
We survey what is actually installed, build the maintenance schedule around it, and give you records an auditor can read without you preparing anything first.